Simrad AP50 Installation Manual Page 39

  • Download
  • Add to my manuals
  • Print
  • Page
    / 134
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 38
Simrad AP50 Autopilot
30 20222469 / B
On-Off
Vsys+
JUNCTION UNIT
MAIN PCB
ROBNET
Bus+
Vsys
Alarm
Wh
Bn Gn
Bus
Pnk
Gry
Yel
AP51
CONTROL UNIT
JP21
JACKPOINT
7m cable7m cable
Figure 2-24 JP21 Jack Point Mounting
2.12 RC25 Rate Compass
Figure 2-25 RC25 Rate Compass Mounting
The heading sensor is the most important part of the AP50
system and great care must be taken in choosing the mounting
location. The heading sensor can be mounted at any location
where there is a minimum of magnetic interference and
minimum movements. It is not recommended to use the RC25
on steel vessels. However, if this is done, it should be installed 1
meter above the steel deck to obtain optimum performance.
Note ! In order to prevent excessive movements, an autopilot heading
sensor should not be installed on the fly bridge or on the mast.
The rate compass can be deck-mounted or on the bulkhead,
athwartship or alongship. The heading offset feature of the
AP50 will compensate for the mechanical offsets that may be a
result of the selected location and orientation of the RC25.
Page view 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 133 134

Comments to this Manuals

No comments